MOT2K 2000 AMP TEST SET
The MOT2K is a light circuit breaker test set
capable of delivering 2000 AMPS of short circuit
current. In addition, the MOT2K sources and measures
AC voltage in ranges of 0 to 300 and 0 to 600 VAC.
It also features a 0 to 175V DC supply suitable for
circuit breaker minimum trip and operate time tests.
The MOT2K measures voltage, current and elapsed time.
SCROLL DOWN FOR MORE INFO !!
Photo below shows main power-up menu of MOT2K. The operator can select
AC Amps, AC volts, or DC volts.
Photo below shows AC current sub-menu of the MOT2K. The operator can select
from two voltage taps, 24V and 5V with two current ranges on each tap.
Photo below shows AC current mode of the MOT2K. The operator can perform time
element tests to 1000 AMPS and instantaneous and short time element
tests to 2000 AMPS.
Timer mode can be selected to stop on operation
of an "A" contact, a "B" contact, or a protective device trip that opens the current
circuit. The action that stopped the timer will be displayed on the screen.
Contact LED illuminates on continuity between the timer stop input terminals
allowing convenient sensing of operate point.
Photo below AC voltage mode of the MOT2K. The test set will source voltages
to 600VAC in two ranges. Operate time of voltage relays can be measured.
Photo below shows DC mode of the MOT2K. The test set will source DC voltages
to 170VAC with a rated continuous current of 4A. 12A is available for
.5 seconds to facilitate breaker trip testing. Breaker operation may be timed
and a pulse mode permits consistent measurement of minimum trip voltage without
the danger of damage to the trip coil that might otherwise be caused by
extended application of voltage below the operate point. Both DC current
and voltage are measured and displayed. This DC source is balanced to ground,
filtered, and suitable for powering switchgear and protective relay systems for
test purposes.
The MOT2K performs the following tests and functions
Test simple overcurrent relays.
Test motor protection (thermal overload) relays.
Test low voltage ground fault devices at up to 2000 AMPS.
Test low voltage circuit breakers up to 300 AMPS.
Test AC and DC over and under voltage relays at up to 600 volts AC, 175VDC.
Supply power for test of control circuits and other general uses.
Supply an ungrounded (balanced to ground)
DC source for powering 125V, 48V, and 24V
DC devices and switchgear for test purposes.
Perform as an emergency 125V or 48V battery charger.
Perform minimum trip and close tests of DC operated circuit breakers.
Time the operation of DC operated circuit breakers.
Perform pickup and dropout tests of AC and DC operated relays.
Calibrate and verify time delay relays in industrial control circuits, AC or DC.
The MOT2K provides the following output ratings
0 to 5VAC at 200 AMPS continuous, 2000 AMPS momentary; meter
0 to 200 and 0 to 2000 amps, 0.75% of reading.
0 to 24VAC at 400 AMPS continuous, 200 AMPS momentary; meter
0 to 20 and 0 to 200 amps, 0.75% of reading.
0 to 300VAC at 3 AMPS continuous, 20 AMPS momentary; meter
0 to 300VAC, 0.75% of reading.
0 to 600VAC at 1.5 AMPS continuous, 10 AMPS momentary; meter
0 to 600VAC, 0.75% of reading.
0 to 175VDC at 5 AMPS continuous, 20 AMPS momentary; meter
0 to 200VDC, 0.5% of reading.