This mode meters the current output at
the X1-X2 terminals and the current input at
the I terminals or clamp on.
The unit also measures the angle between these
currents. The hardwire or clamp input is
selected from an easy to use menu screen.
A current may then be injected at the CT
terminals and its amplitude and direction verified
in a relay or other component. The angle reading
allows verification of connection in all cases
including those where a WYE or DELTA connection
is made in a remote junction box. This test proves
continuity and correct connection to meters
and relays prior to energizing equipment. Current
is sourced by the 0-200V output
allowing a long modified extension cord to be used
as a test lead, sufficient current may be injected
using hundreds of feet of light gauge wire if necessary.